Conventions and units#

Units#

All values are computed in SI base units, as f64:

Quantity Computed in Typical display (metric / US)
Length m m / ft
Area m² mm² / in² (kcmil for conductors)
Force (tension, point load) N kN / lbf
Force per length (weight, wind, ice, distributed load) N/m N/m / lbf/ft
Stress, pressure, modulus Pa MPa / psi
Mass per length kg/m kg/m / lbm/ft
Angle rad °
Speed m/s m/s / mph
Temperature K °C / °F
Second moment of area, torsion constant m⁴ cm⁴ / in⁴
Section modulus m³ cm³ / in³

What the files store differs for two quantities, so that they read naturally:

  • Line model (line file, OHL XML, project tables): plain SI numbers, except angles in degrees (fields ending in _deg) and temperatures in °C. Voltages are in kV (_kv) and frequencies in Hz (_hz).
  • Library files (TOML: cables, insulators, structure types, weather and load cases): every value carries its unit as text ("12.5 m", "20 °C", "30 deg"), any supported unit, converted to SI when read.

The conversion to radians and kelvin happens when the files are read; nothing is stored in radians or kelvin.

Conversion factors are the exact definitions (international foot = 0.3048 m, avoirdupois pound = 0.453 592 37 kg, standard gravity \( g_n = 9.806\,65 \) m/s²). They are checked against NIST SP 811 in the validation suite.

The type system enforces dimensional consistency, e.g. a distributed load times a length is a force:

\[ F = w \, L \qquad [\mathrm{N}] = [\mathrm{N/m}] \cdot [\mathrm{m}] \]

and a wind pressure on a conductor diameter is a load per unit length:

\[ w_{wind} = q \, d \qquad [\mathrm{N/m}] = [\mathrm{Pa}] \cdot [\mathrm{m}] \]

Numerical exit clauses#

Every iterative method documented in this manual states its convergence criterion and its iteration and time limits. When a limit is reached the calculation fails with an explanation instead of returning an unconverged value (see Performance and time budgets).

Coordinate conventions#

  • Project coordinates: a projected coordinate system in metres (the line's crs, e.g. EPSG:2056); x east, y north, z up. Heights are kept as given — usually orthometric — and no geoid model is applied (Coordinate systems).
  • Stations and offsets: stations are measured along a route's alignment (or its structures); offsets are positive to the right looking ahead (Line files).
  • Structure axes: origin at the structure's ground centre; x to the right of the line (transverse), y ahead (along the line), z up. orientation_deg is the direction of the local x axis, degrees counter-clockwise from east.
  • Angles around a structure as shown in the app (string directions, Structures › Angles around structures) turn clockwise seen from above, with ahead at the project's angle (the line's display setting ahead_deg, 0° by default; e.g. 270: ahead 270°, right 0°): right is ahead + 90°, back ahead + 180°, left ahead + 270°. This is a display convention only; stored positions do not depend on it.
  • Wind comes from the left or the right of the line, looking ahead along it: along its routes' alignments (the nearest segment), whichever way a section or a jumper was entered. A section whose points run against the line is solved with the side swapped, so all spans blow to the same side. The wind acts horizontally, perpendicular to each span. A jumper takes the line's wind across itself: the part normal to it, by \( \cos^2 \) of the angle between the wind and its normal, so all of it for a jumper along the line, little for one across it.
  • Structure loads are given in the line's axes (x, y, z) and in the structure's axes: transverse, longitudinal (ahead) and vertical (down) — see Load cases.